LT/MV PANELS
LT Panels
- Rated current upto 6300A
- Fault level upto 100kA for 1sec
-
Construction of panel: 2A/2B/3A/3B/4A/4B
- Seismic zone IV & V certified
-
Degree of protection: IP 42 / IP 52 / IP 54 / IP 65
- Bus bar: Aluminium or Copper
- Interleaved design of main bus bar for ratings above 3200A
-
Panels are functionally color coded for easy identification of
feeders Transformer I/C Feeder - Blue, Diesel Generator
Incomer Feeder - Orange, Bus Coupler Feeder -
Off White, O/G Feeders- Siemens Grey RAL-7032
MV Panels
- Voltage rating – 6.6kV/11kV / 22kV / 33kV
-
Current rating – 6.6kV/11kV- up to 3150A
22kV / 33kV – 1250A
-
Fault level – 11KV panels - 20kA / 26.3kA / 31.5kA / 40kA for 3
sec 33KV panels – 31.5kA for 3sec
- Internal arc tested
-
Degree of protection:
Indoor panel – IP 4X Outdoor Panel – IP 55
-
Overall dimensions:
For 11kV (26.3kA) - Width: 600mm; Height: 2350mm; Depth:
1500mm
-
For 11kV (40kA) - Width: 800mm; Height: 2350mm; Depth:
1500mm
-
For 33kV (31.5kA) - Width: 1000mm; Height: 2700mm; Depth:
2100mm
- Conforms to IS & IEC standards and is fully type tested