LT/MV Panels

LT/MV PANELS

LT Panels

  • Rated current upto 6300A
  • Fault level upto 100kA for 1sec
  • Construction of panel: 2A/2B/3A/3B/4A/4B
  • Seismic zone IV & V certified
  • Degree of protection: IP 42 / IP 52 / IP 54 / IP 65
  • Bus bar: Aluminium or Copper
  • Interleaved design of main bus bar for ratings above 3200A
  • Panels are functionally color coded for easy identification of feeders Transformer I/C Feeder - Blue, Diesel Generator Incomer Feeder - Orange, Bus Coupler Feeder - Off White, O/G Feeders- Siemens Grey RAL-7032


MV Panels

  • Voltage rating – 6.6kV/11kV / 22kV / 33kV
  • Current rating – 6.6kV/11kV- up to 3150A 22kV / 33kV – 1250A
  • Fault level – 11KV panels - 20kA / 26.3kA / 31.5kA / 40kA for 3 sec 33KV panels – 31.5kA for 3sec
  • Internal arc tested
  • Degree of protection: Indoor panel – IP 4X Outdoor Panel – IP 55
  • Overall dimensions: For 11kV (26.3kA) - Width: 600mm; Height: 2350mm; Depth: 1500mm
  • For 11kV (40kA) - Width: 800mm; Height: 2350mm; Depth: 1500mm
  • For 33kV (31.5kA) - Width: 1000mm; Height: 2700mm; Depth: 2100mm
  • Conforms to IS & IEC standards and is fully type tested